Monitoring The Upper Endstop 'G.\\Open - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

F2.LEVL2 - threshold 2
Adjustment range:
Purpose:
Factory setting:
F3.LEVL3 - threshold 3
Adjustment range:
Purpose:
Factory setting:
9.4.3.7

Monitoring the upper endstop 'G.\\OPEN'

G. OPEN - Monitoring of upper endstop
Note
Fault detection
Monitoring of upper endstop not only responds to faults in the valve. If the limit thresholds of
the upper endstop are exceeded due to misalignment of the position feedback, the
misalignment also triggers a message.
Requirement:
Possible settings:
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
0.1 ... 10.0
Use this sub-parameter to set threshold 2 for the lower endstop in
percent. Set the threshold in a range from '0.1' to '10.0'.
The positioner triggers a threshold 2 message if the difference be‐
tween the lower endstop and the initialization value undershoots
threshold 2. This message is only output if threshold 3 is not under‐
shot at the same time. The process to activate and display this mes‐
sage is described in the 'XDIAG' parameter.
2.0
0.1 ... 10.0
Use this sub-parameter to set threshold 3 for the lower endstop in
percent. Set the threshold in a range from '0.1' to '10.0'.
The positioner triggers a threshold 3 message if the difference be‐
tween the lower endstop and the initialization value undershoots
threshold 3. The process to activate and display this message is
described in the 'XDIAG' parameter.
4.0
The '52.XDIAG' Activating for extended diagnostics (Page 166) pa‐
rameter is set to 'On1', 'On2' or 'On3'.
The '39.YCLS' Tight closing/fast closing with manipulated variable
(Page 157) parameter is set to one of the following values: 'uP',
'uP do', 'Fu', 'Fu Fd', 'uP Fd', 'Fu do'
● OFF
● On
Parameter assignment
9.4 Description of parameters
181