C4.FACT3 - Factor 3
Adjustment range:
Purpose:
Factory setting:
See also
11 Monitoring/compensation of pneumatic leakage (Page 219)
9.4.3.4

Monitoring of stiction (slipstick) 'd.\\STIC'

d. STIC - Monitoring of stiction (slipstick)
Requirement:
Possible settings:
Purpose:
Factory setting:
Note
Incorrect interpretation in case of travel times below one second
If the travel times are less than one second, the positioner does not accurately differentiate
between a normal movement of the actuator and a sudden change. Therefore, increase the
travel time if required.
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
0.1 ... 100.0
Use this sub-parameter to set the factor for formation of threshold 3.
Set the factor in a range from '0.1' to '100.0'. The threshold is the
product of 'C1.LIMIT' and 'C4.FACT3'.
A leakage was detected when threshold 3 is exceeded. The control
quality is strongly affected. Maintenance is necessary. The thresh‐
old 3 message is shown.
The process to activate and display this message is described in the
'XDIAG' parameter.
2.0
The '52.XDIAG' Activating for extended diagnostics (Page 166) pa‐
rameter is set to 'On1', 'On2' or 'On3'.
● OFF
● On
Use this parameter to continuously monitor the current stiction (slip‐
stick) of the control valve. If the parameter is activated, the positioner
detects the slipstick that may occur. Sudden changes in the valve
position, so-called slip jumps, indicate excessive stiction. Where slip
jumps are detected, the filtered step height is stored as a slipstick
value. If slip jumps no longer exist, the stiction (slipstick) is reduced
slowly. Monitoring is performed in three steps. To activate monitor‐
ing, set the parameter to 'On'. Sub-parameters are displayed. Ap‐
propriately set the sub-parameters.
The current value is displayed in Diagnostic value '17.STIC - Stiction
(slipstick)' (Page 205). The positioner triggers a message if the cur‐
rent value exceeds one of the thresholds.