Parameter assignment
9.4 Description of parameters
9.4.2.16

'45.A1' / '46.A2' Response threshold of alarm

Adjustment range:
Purpose:
Factory setting:
9.4.2.17

'47.\\FCT' Function for fault message output

Requirement:
Possible settings:
Purpose:
Factory setting:
162
0.0 ... 100.0
These parameters are used to specify when an alarm should be
displayed. The response thresholds of the alarms (in percent) refer
to the MPOS scale in the '37.YNRM' Standardization of manipulated
variable (Page 155) parameter. The MPOS scale corresponds to
the mechanical travel.
Depending on the setting of the alarm function in the '44.AFCT'
Alarm function (Page 160) parameter, the alarm is triggered upon
an upward violation (Max) or downward violation (Min) of this re‐
sponse threshold.
With 'A1': 10.0
At least one of the following modules is fitted
● Alarm module
● Slot initiator alarm module (SIA module)
● Mechanical limit switch module
Normal direction of action
nA
nAb
The fault message in the form of monitoring of control deviation over
time can also be triggered due to the following events:
● Power failure
● Processor fault
● Actuator fault
● Valve fault
● Compressed air failure
● Threshold 3 message of extended diagnostics.
See parameter '52.XDIAG' Activating for extended diagnostics
(Page 166).
The fault message cannot be switched off, but it can be suppressed
(factory setting) when you exit 'Automatic' mode. Set the ' FCT' pa‐
rameter to ' nA' to also generate a fault message here.
You also have an option to "or" the fault message with the status of
the binary inputs. To do this, first set the '42.BIN1' / '43.BIN2' Func‐
tion binary input (Page 159) parameter to 'on' or '-on'. Subsequently
set the ' FCT' parameter to ' nAb'.
Select the '- ' setting if you want the fault message to be output with
inverted direction of action.
With 'A2': 90.0
Inverted direction of action
● -
● - nA
● - nAb
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC