Advertisement

Note
If the extended diagnostic is activated using parameter "'52.XDIAG' Activating for extended
diagnostics (Page 166)" with setting "On3", then the alarms are not output through the alarm
module. Alarm A1 is output with setting "On2". However, notification via the communication
interface is possible at any time.
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
Direction of action and hysteresis
Parameter assignment
9.4 Description of parameters
Alarm module
Examples
A1
A1 = 48
AFCT = MIN / MAX
A2 = 52
Way =45
Active
Way =50
Way =55
A1 = 48
AFCT = -MIN / -MAX
A2 = 52
Way =45
Way =50
Active
Way =55
Active
A1 = 52
AFCT = MIN / MAX
A2 = 48
Way =45
Active
Way =50
Active
Way =55
A1 = 52
AFCT = -MIN / -MAX
A2 = 48
Way =45
Way =50
Way =55
Active
A2
Active
Active
Active
Active
Active
Active
161