The value in the 'YCDO' parameter is always smaller than that in 'YCUP'. The tight closing/fast
closing function has a fixed hysteresis of 1%. The 'YCUP' parameter is relative to the
mechanical stops. The 'YCUP' is independent of the values set in the '7.SDIR' Setpoint
direction (Page 151) and '38.YDIR' Direction of manipulated variable for display and position
feedback (Page 157) parameters.
9.4.2.14

'42.BIN1' / '43.BIN2' Function binary input

Setting option
Purpose:
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
● Binary input 1
Normally open
OFF
on
bloc1
bloc2
uP
doWn
StoP
PST
● Binary input 2
Normally open
OFF
on
uP
doWn
StoP
PST
These parameters determine the function of the binary inputs. The
possible functions are described below. The direction of action can
be adapted to a normally closed or normally open mode.
● BIN1 or BIN2 = On or -On
Binary messages from peripherals, e.g. from pressure or
temperature switches, are read over the communication
interface or fed through a logical OR combination with other
messages to trigger the error message output.
● BIN1 = bLoc1
Use this parameter value to interlock the "Configuration" mode
against adjustment. The lock is performed e.g. with a jumper
between terminals 9 and 10.
● BIN1 = bLoc2
If binary input 1 has been activated, the "Manual" as well as
"Configuration" modes are blocked.
Parameter assignment
9.4 Description of parameters
Normally closed
OFF
-on
-uP
-doWn
-StoP
-PST
Normally closed
OFF
-on
-uP
-doWn
-StoP
-PST