'38.YDIR' Direction of manipulated variable for display and position feedback

Possible settings:
Purpose:
Factory setting:
9.4.2.11

'39.YCLS' Tight closing/fast closing with manipulated variable

Possible settings:
Purpose:
Factory setting:
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
● riSE
● FALL
This parameter is used to set the direction of action of the display
and the position feedback I
riSE
no
None
uP
Tight closing Up
do
Tight closing Down
uP do
Tight closing Up and Down
Fu
Fast closing Up
Fd
Fast closing Down
Fu Fd
Fast closing Up and Down
uP Fd
Tight closing Up and fast closing Down
Fu do
Fast closing Up and tight closing Down
This parameter is used to drive the control valve to the mechanical
end stops. If the parameter is not activated, the control valve controls
to the end positions which were determined during the initialization.
With tight closing, the control valve requires longer to leave the end
stops. With fast closing, the end stops of the control valve are left
immediately.
The tight closing and fast closing functions are activated on one side
or for both end positions. Parameter '39.YCLS' becomes effective
if the effective setpoint:
● Is at or below the value set in the '40.YCDO' parameter.
● Is at or above the value set in the '41.YCUP' Value for tight
closing/fast closing Up (Page 158) parameter.
no
Parameter assignment
9.4 Description of parameters
. The direction can be rising or falling.