9.4.2.2
'7.SDIR' Setpoint direction
Possible settings:
Purpose:
Factory setting:
9.4.2.3
'8.SPRA' Setpoint split range start / '9.SPRE' Setpoint split range start end
Adjustment range:
Purpose:
Factory setting:
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
● riSE
● FALL
This parameter is used to set the setpoint direction. The setpoint
direction is used to reverse the direction of action of the setpoint.
● Rising (riSE): A higher value at the setpoint input results in
opening of the valve.
● Falling (FALL): A higher value at the setpoint input results in
closing of the valve.
The setpoint direction is primarily used for the split-range mode and
for single-acting actuators with the safety setting 'uP'.
riSE
0.0 ... 100.0
With these two parameters in combination with parameter "'7.SDIR'
Setpoint direction (Page 151)", you can limit the effective setpoint.
This allows split range tasks with the following characteristic curves
to be solved:
● rising/falling
● falling/rising
● falling/falling
● rising/rising
With "SPRA": 0.0
Parameter assignment
9.4 Description of parameters
With "SPRE": 100.0
151