Parameter assignment
9.4 Description of parameters
9.4.1.4

'4.INITA' Initialization (automatically)

Possible settings:
Purpose:
Factory setting:
9.4.1.5

'5.INITM' Initialization (manual)

Possible settings:
Purpose:
Description:
Factory setting:
9.4.2

Application parameters 6 to 52

9.4.2.1

'6.SCUR' Current range of setpoint

Requirement:
Possible settings:
Purpose:
Factory setting:
150
● NOINI
● no / ###.#
● Strt
Use this parameter to start the automatic initialization process.
1. Select the "Strt" setting.
2. Then press the
button for at least 5 seconds.
The sequence of the initialization process from "RUN 1" to "RUN 5"
is output in the bottom line of the display.
NOINI
● NOINI
● no / ###.#
● Strt
Use this parameter to start the manual initialization process.
1. Select the "Strt" setting.
2. Then press the
button for at least 5 seconds.
If the positioner has already been initialized and if the "4.INITA" and
"5.INITM" values are set, it is possible to reset the positioner to the
non-initialized status. To do this, press the
seconds.
NOINI
● You have a SIPART PS2 in version "2-, 3-, 4-wire".
● Positioner is connected in accordance with the connection
graphics for 2/3/4-wire systems shown in section "Electrical
wiring (Page 77)".
● 0 MA
● 4 MA
This parameter is used to set the current range of the setpoint. The
selection of the current range depends on the type of connection.
The "0 MA" setting (0 to 20 mA) is only possible for three-wire and
four-wire connections.
4 MA
button for at least 5
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC