Parameter
12.SFCT
13.SL0 ...
33.SL20
13.SL0
14.SL1 ....
32.SL19
33.SL20
34.DEBA
35.YA
36.YE
37.YNRM
38.YDIR
39.YCLS
40.YCDO
41.YCUP
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
Function
Setpoint function
Linear
Equal percentage
Inverse equal percent‐
age
Freely adjustable
Setpoint turning point
1)
At
0 %
5 % ...
95 %
100 %
Deadband of closed-loop controller
Start of manipulated variable limit
End of manipulated variable limit
Standardization of manipulated variable
To mechanical travel
To flow
Direction of action of manipulated variable for display and position feedback
Rising
Falling
Tight closing/fast closing with manipulated variable
None
Tight closing Up
Tight closing Down
Tight closing Up and Down
Fast closing Up
Fast closing Down
Fast closing Up and Down
Tight closing Up and fast clos‐
ing Down
Fast closing Up and tight clos‐
ing Down
Value for fast closing/tight closing
Down
Value for fast closing/tight closing Up
9.3 Tabular overview of the parameters
Parameter values
Lin
1 : 25
1 - 25
1 : 33
1 - 33
1 : 50
1 - 50
25 : 1
n1 - 25
33 : 1
n1 - 33
50 : 1
n1 - 50
FrEE
0.0 ... 100.0
Auto / 0.1 ... 10.0
0.0 ... 100.0
0.0 ... 100.0
MPOS
FLoW
riSE
FALL
no
uP
do
uP do
Fu
Fd
Fu Fd
uP Fd
Fu do
0.0 ... 0.5 ... 100.0
0.0 ... 99.5 ... 100.0
Parameter assignment
Unit
%
%
%
%
%
%
141