7.5 Commissioning linear actuators
5. Call the "4.INITA" parameter. To do this, briefly press the
following:
6. Start the initialization process. To do this, keep the
until the display shows the following:
The positioner runs through five initialization steps during the automatic initialization
process. Displays for the initialization steps from "RUN 1" to "RUN 5" are shown in the lower
line on the display. The initialization process depends on the actuator used, and takes up
to 15 minutes.
7. The following display indicates that the automatic initialization is complete:
Aborting the automatic initialization process
1. Press the
The positioner is in the "Configuration" mode.
2. Exit the "Configuration" mode. To do this, keep the
The software status is displayed.
After releasing the
initialized.
See also
Sequence of automatic initialization (Page 108)
118
button. The display shows the following:
button, the positioner is in "P manual mode". The positioner is not
button. The display shows the
button pressed for at least 5 seconds
button pressed for at least 5 seconds.