Commissioning Linear Actuators; Preparing Linear Actuators For Commissioning - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

7.5

Commissioning linear actuators

7.5.1

Preparing linear actuators for commissioning

Requirements
You have already installed the positioner using the suitable mounting kit.
Setting the transmission ratio selector
Note
Commissioning
The setting of the transmission ratio selector is extremely important to commission the
positioner.
Connecting the positioner
1. Connect a suitable current or voltage source. The positioner is now in "P manual mode".
The current potentiometer voltage (P) in percent is shown in the upper line of the display,
e.g.: 'P37.5', and 'NOINI' flashes in the bottom line:
2. Connect the actuator and the positioner to the pneumatic lines.
3. Supply the pneumatic auxiliary power to the positioner.
SIPART PS2 with and without HART
Operating Instructions, 05/2017, A5E00074631-AC
Stroke [mm]
5 ... 20
25 ... 35
40 ... 130
7.5 Commissioning linear actuators
Position of the transmission ratio selector
33°
90°
90°
Commissioning
115

Advertisement

Table of Contents
loading

Table of Contents