Immergas VICTRIX MAIOR 35 X TT 1 ERP Instruction And Recommendation Booklet

Immergas VICTRIX MAIOR 35 X TT 1 ERP Instruction And Recommendation Booklet

Hide thumbs Also See for VICTRIX MAIOR 35 X TT 1 ERP:
Table of Contents

Advertisement

VICTRIX MAIOR
Instruction and
IE
recommendation booklet
35 X TT 1 ERP

Advertisement

Table of Contents
loading

Summary of Contents for Immergas VICTRIX MAIOR 35 X TT 1 ERP

  • Page 1 VICTRIX MAIOR Instruction and recommendation booklet 35 X TT 1 ERP...
  • Page 3 Read the following pages carefully: you will be able to draw useful suggestions regarding the correct use of the appliance, the respect of which, will con rm your satisfaction for the Immergas product.
  • Page 4: Table Of Contents

    3.6 Checks following conversion 1.8 External temperature probe (Optional)... 9 2.9 System draining..........25 to another type of gas........28 1.9 Immergas ue systems........10 2.10 Anti-freeze protection........25 3.7 Calibration type involving 1.10 Tables of resistance factors 2.11 Case cleaning.
  • Page 5: Boiler Installation

    RECOMMENDATIONS. tions; otherwise, the manufacturer cannot be e Victrix Maior 35 X TT 1 ErP boiler has been held responsible for any damage caused to the designed for wall mounted installation only, to household appliances.
  • Page 6: Main Dimensions

    Immergas boilers withstand ethylene and e water in the storage tank unit is not protected propylene glycol based antifreeze liquids (if the against freezing when the boiler is switched o .
  • Page 7: Gas Connection

    Ensure correct gas cock connection. e gas sup- Attention: Immergas declines all liability in the ply pipe must be suitably dimensioned according event of damage caused by the inclusion of auto- to current regulations in order to guarantee cor- matic lling that is not its own brand.
  • Page 8: Electrical Connection

    The climate chrono-thermostat Attention: Immergas S.p.A. declines any respon- temperature adjustment range “t0” and “t1” incorporated into the remote panel enables sibility for damage or physical injury caused by (Par.
  • Page 9: External Temperature Probe Optional

    Immergas chrono-thermostats. correlation between system ow temperature and external temperature is determined by the position of the central heating selector switch on...
  • Page 10: Immergas Ue Systems

    Attention: the boiler must be installed ex- element in order to ensure sealing e ciency of clusively with an original Immergas “Green the coupling. Range” inspectionable air intake device and Attention: if the exhaust terminal and/or...
  • Page 11 Resistance Equivalent length Equivalent Equivalent length Equivalent length TYPE OF DUCT Factor in m of concentric length in metres in metres of pipe in m of concentric pipe Ø 60/100 of pipe Ø 80 Ø 60 pipe Ø 80/125 Intake m 7.3 Concentric pipe Ø...
  • Page 12: Outdoor Installation In A

    (B ) or this con guration the upper cover kit guaran- via an Immergas ducting system (B tees additional protection for the boiler. It is The technical regulations in force must be recommended but not compulsory.
  • Page 13: Concentric Horizontal Kit Installation

    Make sure that the external silicone wall concentric bend leaving the boiler. If addi- Immergas also provides a Ø 60/100 simpli ed sealing plate is properly inserted in the wall. tional components are assembled, the length...
  • Page 14: Concentric Vertical Kit Installation

    1.13 CONCENTRIC VERTICAL KIT male side (5) (smooth) into the ange (2) up to Position the xed half-shell (5) on the aluminium INSTALLATION. the end stop; making sure that the wall sealing tile and insert the intake-exhaust pipe (7). Fit the Type C configuration, sealed chamber and plate has been tted (3), this will ensure sealing Ø...
  • Page 15: Separator Kit Installation

    1.14 SEPARATOR KIT INSTALLATION. internal wall sealing plate has been tted, this Type C configuration, sealed chamber and will ensure sealing and joining of the elements fan assisted. making up the kit. • Installation clearances (Fig. 1-21). e mini- Separator kit Ø 80/80. is kit allows air to come mum installation clearance measurements of in from outside the building and the fumes to exit...
  • Page 16: Adaptor C9 Kit Installation

    - Mount the cover (A) complete with adaptor (1) To determine the C ue system in con gura- is kit allows an Immergas boiler to be installed and caps (6) on the wall and assemble the ue tions other than that described (Fig. 1-25) in "C...
  • Page 17: Ducting Of Ues Or Technical Slots

    Multiple and combined ues must be specially Ø 80 exible “Green Range” ducting systems must INDOORS. designed according to the calculation method only be used for domestic use and with Immergas e appliance can be installed inside buildings and requirements of the technical standards condensing boilers.
  • Page 18: Water Treatment System Lling

    - Clean the new system with a suitable cleaning operation check that this no longer occurs. activate the Immergas warranty. e test certi cate device (for example Sentinel X300, Fernox means that the drain trap is lled with conden- and warranty is issued to the user.
  • Page 19: Circulation Pump

    Immergas supplies with instructions for assembly and use. indicated above. zone system kits by request.
  • Page 20: Boiler Components

    1.27 BOILER COMPONENTS. 1-29 Key: 10 - Flue probe 20 - 3 bar safety valve 1 - System draining valve 11 - Sample points (air A) - ( ue gas F) 21 - By-pass 2 - Storage tank return ow by-pass 12 - Burner cover 22 - 3-way valve (motorised) 3 - Gas valve...
  • Page 21: Use And Maintenance Instructions

    In the event of work or maintenance to structures Immergas. We recommend stipulating a yearly company to replace it; near ducting or ue extraction devices and their...
  • Page 22: Using The Boiler

    Attention: or domestic hot water production) the boiler the Victrix Maior 35 X TT 1 ErP boiler was de- • “O ” mode. By holding the button (6) down signed to operate as an appliance for room central goes to “standby” function, equivalent to the for 8 seconds, the display switches-o and the boiler being powered without presence of ame.
  • Page 23 Error Anomaly signalled Cause Boiler status / Solution Code Check on the boiler pressure gauge (1) that Insu cient system Water pressure inside the central heating circuit that is su cient to the system pressure is between 1÷1.2 bar pressure guarantee the correct operation of the boiler is not detected.
  • Page 24 Error Anomaly signalled Cause Boiler status / Solution Code Missing calibration is detected by the P.C.B. It may occur in the Complete calibration event the P.C.B. is replaced or if the parameters are altered in the air e boiler does not start (1) required / gas section, thus requiring “complete calibration”.
  • Page 25: Information Menu

    2.10 ANTI FREEZE PROTECTION. 2.11 CASE CLEANING. Switch the boiler o by putting it in “o ” mode, e “Victrix Maior 35 X TT 1 ErP” series boiler Use damp cloths and neutral detergent to clean disconnect the onmipolar switch outside of the has an anti-freeze function that switches the the boiler casing.
  • Page 26: Boiler Commissioning Initial Check

    BOILER COMMISSIONING - switch the boiler on and check correct ignition; - check the production of DHW (when the boiler is connected to an external storage tank INITIAL CHECK - check the CO ow rate in the ue: unit); - maximum (100%) To commission the boiler: - check sealing e ciency of water circuits;...
  • Page 27: Wiring Diagram

    3.2 WIRING DIAGRAM. Storage tank unit (when the boiler is connected must be connected to clamps 41 and 44 of the e connector X5 is used for the connection to to the external storage tank unit): the boiler is set terminal board (located in the boiler control the relay board.
  • Page 28: Removable Memory

    3.3 REMOVABLE MEMORY - Frequent interventions of the overheating - Poor production of DHW (when the boiler is e P.C.B. is equipped with a removable memory safety thermostat. It can depend on the lack connected to an external storage tank unit);. If a (2 Fig.
  • Page 29: Calibration Type Involving

    3.7 CALIBRATION TYPE INVOLVING In order to access the complete calibration • Intermediate heat output ignition: once the stage, you must switch the boiler on, set the THE REPLACEMENT OF A nominal heat output calibration is con rmed, DHW selector in the “6 o' clock” position and COMPONENT.
  • Page 30: Adjusting The Air Gas Ratio

    (nominal, intermediate and minimum) progress automatically and you Victrix Maior 35 X TT 1 ErP must wait until calibration is complete. - To increase the combustion setting, press the...
  • Page 31: Programming The P.c.b

    3.12 PROGRAMMING THE P.C.B. Attention: if necessary the default values relating e boiler is prepared for possible programming to parameters “S” and “P0 ÷ P2” can be altered by of several operation parameters. By modifying temporarily modifying the type of gas (parameter these parameters as described below, the boiler “G”) and by restoring it according to the actual can be adapted according to speci c needs.
  • Page 32 Customised Parameter Description Range Default Parameter value De nes the maximum heat output percentage of the boiler during the D.H.W. DHW max 0 - 99 % phase compared to the maximum heat output available De nes the minimum heat output percentage of the boiler compared to the Min output 0 - P2 minimum heat output available...
  • Page 33 Customised Parameter Description Range Default Parameter value Central heating set point minimum De nes the minimum ow temperature. 20 ÷ 50 °C temperature Central heating set (t0+5) ÷ point maximum De nes the maximum ow temperature. 85 °C temperature Establishes the boiler ignition and switch-o mode in DHW mode. On = -3 °C 0 - Ignition occurs when the water contained in the storage tank drops by 3 °C O = +0 °C...
  • Page 34: Solar Panels Coupling Function

    Customised Parameter Description Range Default Parameter value Hydraulic model De nes the type of hydraulics in the boiler Not used on this boiler model Model De nes the type of circulator in the boiler Pump Maximum pump Sets the maximum pump operating speed 1 ÷...
  • Page 35: Yearly Appliance Check And Maintenance

    / detection electrode and, if required, change it, also changing the relative gasket. At this point, activate the “complete calibration” function. Victrix Maior 35 X TT 1 ErP at nominal at intermediate at minimum...
  • Page 36: Casing Removal

    3.21 CASING REMOVAL. 6) Pull the front panel (e) towards you and To facilitate boiler maintenance the casing can release it from its lower seat. be completely removed as follows: • Front (Fig. 3-15c). • Lower grid (Fig. 3-15a). 7) Loosen the two screws (g). 1) Loosen the two screws (a);...
  • Page 37 • Control panel (Fig. 3-15d). • Sides (Fig. 3-15e). 9) Press the hooks on the side of the control 11) Loosen screws (k) of side fastening (j). panel (i). 12) Remove the sides by extracting them from 10) Tilt the control panel (i) towards you. their rear seat (Rif.
  • Page 38: Variable Heat Output

    3.22 VARIABLE HEAT OUTPUT. m in length. Gas ow rates refer to net heating N.B.: the power data in the table has been ob- value below a temperature of 15°C and at a pres- tained with intake-exhaust pipe measuring 0.5 sure of 1013 mbar.
  • Page 39: Technical Data

    3.24 TECHNICAL DATA. Nominal heat input kW (kcal/h) 34.9 (30040) Minimum heat input kW (kcal/h) 3.6 (3109) Nominal heat output (useful) kW (kcal/h) 34.2 (29412) Minimum heat output (useful) kW (kcal/h) 3.5 (3010) (*) E ective thermal e ciency 80/60 Nom./Min. 97.9 / 96.8 (*) E ective thermal e ciency 50/30 Nom./Min.
  • Page 40: Key For Data Plate

    3.25 KEY FOR DATA PLATE. Cod. Md Sr N° Cod. PIN Type n min. max. n min. n max. Class CONDENSING N.B.: the technical data is provided on the data plate on the boiler. Model Cod. Md Model code Sr N° Serial Number Check Cod.
  • Page 41: Technical Parameters For Combination Boilers In Compliance With Regulation 813/2013

    Contact information IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY (*) High temperature mode means 60°C on return and 80°C on ow. (**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return tem- perature.
  • Page 42: Parameters For Lling In

    In case you should wish to install an assembly, Use sheet g. 3-18 for “assemblies” related to starting from the Victrix Maior 35 X TT 1 ErP the heating function (e.g.: boiler + temperature boiler, use the assembly charts in g. 3-18 and controller).
  • Page 43 Parameters for lling in the assembly chart. Parameter Victrix Maior 35 X TT 1 ErP ‘I’ ‘II’ ‘III’ 0.79 ‘IV’ 0.31 * to be established by means of table 5 of Regulation 811/2013 in case of “assembly” including a heat pump to integrate the boiler.
  • Page 44 Facsimile for lling in domestic hot water production system package che. 3-19...
  • Page 45 Parameters for lling in DHW package assembly chart. Parameter Victrix Maior 35 X TT 1 ErP ‘I’ ‘II’ ‘III’ * to be determined according to Regulation 811/2014 and transient calculation methods as per Notice of the European Community no. 207/2014.
  • Page 48 Follow us Immergas Italia immergas.com Immergas S.p.A. 42041 Brescello (RE) - Italy Tel. 0522.689011 Fax 0522.680617 Certi ed company ISO 9001...