To verify the connection:
1. Press the inverter external LCD light button to display the status screens one after the other:
a. Check the RS485 communication status:
w w w w w w w w
R S 4 8 5 - 1 < M L T > < 0 2 > < 0 2 >
The MLT under Dev denotes that the configuration is for multiple devices.
l
The number under Prot (protocol) should display the number of c onfigured devices.
l
The number under ## should display the number of detected d evices.
l
The above screen shows an example of 2 d evices on the same bus (for example: meter and
battery). If RGM is pre-installed, and a battery and an external meter are also installed, the screen
should show <3><3>.
If the number of devices under Prot does not match the number u nder ##, refer to
Troubleshooting on page 93.
b. Check the meter(s): In the meter(s) status screen check that the status is OK. The following is an
example of the status of an Export (or Export+Import) meter:
E x p o r t
S t a t u s :
P o w e r [ W ] :
E n e r g y [ W h ] :
If Comm. Error appears, refer to Troubleshooting on page 93.
c. Check the battery information: identification, charging status and power, and the operating
mode.
B S N :
S O E :
T o t a l :
S t a t e :
If Comm. Error appears, refer to Troubleshooting on page 93.
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.3
D e v
P r o t
M e t e r
< O K / E r r o r # >
x x x x x . x
X X X X X . X
X X X X X X X X X
I D : 1 5
8 9 %
W W W W
P W R :
< x > W h
C h a r g i n g
Chapter 10: System Configuration
# #
2 W
85