Table of Contents

Advertisement

 4.  Loosen the screws of pins A(+), B(-), and G on the left of the RS485 terminal block (RS485-1 or RS485-2).
 5.  Insert the wire ends into the G, A and B pins shown above. Use Four- or six-wire twisted pair cable for 
this connection. You can use any color wire for each of the A, B and G connections, as long as the 
same color wire is used for all A pins, the same color for all B pins and the same color for all G pins.
 6.  For creating an RS485 bus - connect all B, A and G pins in all inverters. The following figure shows this 
connection schema:
NOTE
Do not cross-connect B, A and G wires.
 7.  Tighten the terminal block screws.  
 8.  Check that the wires are fully inserted and cannot be pulled out easily. 
 9.  Push the RS485 terminal block firmly all the way into the connector on the right side of the 
communication board. 
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.3
Chapter 9: Setting Up Communication to the Monitoring Platform
Figure 39: RS485 terminal block
Figure 40: Connecting the inverters in a chain
79