SolarEdge SE7600A-US Installation Manual page 37

Storedge solution with backup
Hide thumbs Also See for SE7600A-US:
Table of Contents

Advertisement

The following table,     F igure 21 and Figure 22 detail cable types and connections of one battery (LG-chem 
Resu10H).   P repare cables and connect as described in the following table:
StorEdge
Connection Unit
connection
DC
BAT + terminal block
BAT - terminal block
Control and monitoring
5-pin communication
terminal block:
En (Enable)
V+
1
B- (RS485)
1
A+ (RS485)
G (RS485)
1 Must be twisted pair
2 Must be twisted pair
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.3
LG Chem
Connection method
RESU10H
battery
Connection Unit
connection
Insert a flat blade
o
screwdriver into the
square opening at the top
DC+
of the terminal block and
press to open clamp
mechanism.
Insert the wire into the
o
round opening and
DC-
release the screwdriver
to spring back and clamp
the wire.
6-pin connector
Press the protrusion at the
ENABLE_H
top of the terminal block to
Not connected
open the connection hole,
2
RS485_L -
insert the wire and release to
spring back and clamp the
2
RS485_H +
wire.
EN_G
Chapter 6: StorEdge Inverter Connections
Recommended cable
to the
(min-max AWG)
DC cable 10 AWG (10-14
AWG), 600V insulated.
5-wire shielded twisted pair
cable 24 AWG (16-24AWG),
600V insulated.
CAT5 600V insulated can
also be used.
type