SolarEdge SE7600A-US Installation Manual page 18

Storedge solution with backup
Hide thumbs Also See for SE7600A-US:
Table of Contents

Advertisement

Step 1: Mounting and Grounding the Power Optimizers
 
For mounting on a grounded metal rail: Use the provided 5/16'' stainless steel grounding star 
l
washer between the railing and the flat side of the mounting bracket.   T he grounding washer 
should break through the anodize coating of the railing to ensure low resistive connection. Apply 
torque of 9.5 N*m / 7 lb*ft. See Figure 2.
Figure 2: Power optimizer installation and grounding using a star washer
 
For mounting on rails with sliding nut fasteners: If the star washer cannot be used, use the 
l
SolarEdge grounding plate (purchased separately) between the railing and the flat side of the 
mounting bracket. Use mounting specific hardware as needed. Apply torque of 9.5 N*m / 7 lb*ft. 
See Figure 3
Figure 3: Power optimizer installation and grounding using a grounding plate
 
 
For mounting on un-grounded structures (such as a wooden structure): If the star washer or 
l
the plate cannot be used, use the SolarEdge grounding lug (purchased separately) with an  
equipment-grounding conductor   a ccording to the supplied instructions. The grounding terminal 
accepts a wire size of 6-14 AWG, and must be sized for equipment grounding per NEC 250.122 
requirements. Tighten the screws connecting the power optimizer to the frame and the 
grounding terminal screw. Apply torque of 9.5 N*m / 7 lb*ft. See Figure 4
16
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Seauto-tx-5000

Table of Contents