Storedge solution with backup
Hide thumbs Also See for SE7600A-US:
Table of Contents

Advertisement

Problem
No power to the backup loads
while grid is OFF (power outage)
Inverter without auto-transformer
(On-grid only) - The inverter does
not start production and Error 182
Auto-Transformer Temp. Too
High is displayed
A battery internal fault is displayed
on the LCD:Battery Internal
Fault XXXX (ID: XX)
 
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.3
Description or possible cause
The backed-up loads are not
backed up
The thermal sensor cables are not
connected.
Fault # –according to battery
model. ID – battery's Modbus ID.
Appendix A: Troubleshooting
Troubleshooting
Check that the inverter is producing
o
power
Check that the Backup function is
o
enabled (Backup conf è Backup
è Enable).
Check that there are no errors on
o
the inverter LCD
Check the circuit breakers on the
o
backed-up loads AC panel
Check that the AC breaker in the
o
Connection Unit are in the UP
position (see Figure 10)
Check that the AC bypass switch
o
in the Connection Unit is set to
position 1 (see Figure 10) .
Move the DIP switch SW2 in the
Connection Unit to the UP position
(ON) (refer to DIP Switch Setup on
page 38).
Contact SolarEdge Support