Additional StorEdge Troubleshooting

Additional StorEdge Troubleshooting
Some of the troubleshooting procedure may require removing the covers of system components 
(inverter, battery, Connection Unit, or meter). Be sure to disconnect all power sources to avoid 
electrocution.
For opening the cover refer to  on page 44.
WARNING!
ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires when the inverter cover is removed.
RISQUE D'ÉLECTROCUTION, ne touchez pas les fils non isolés lorsque le couvercle de l'onduleur est
retiré.
 
Problem
During normal operation (grid
supplies power), no power to the
backup loads while the inverter is
producing power
98
Description or possible cause
The main circuit breakers or loads
circuit breakers in the backed up
loads panel have been triggered
Internal circuit breaker has been
triggered
The inverter is malfunctioning
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.3
Troubleshooting
Check that the backed-up loads
breakers on the CB panel are in the UP
position
Check that the AC circuit breaker in
the Connection Unit is in the UP
position (see Figure 10)
Restart the inverter
If the problem persists, move the
AC bypass switch in the Connection
Unit to position 2 (see Figure 10) to
supply power to the loads until the
inverter problem is solved (contact
SolarEdge support if required). Then
move to position 1.