46
WT05
Number of operating hours in the actuating range
WT05
47
WT10
Number of operating hours in the actuating range
WT10
48
WT30
Number of operating hours in the actuating range
WT30
49
WT50
Number of operating hours in the actuating range
WT50
50
WT70
Number of operating hours in the actuating range
WT70
51
WT90
Number of operating hours in the actuating range
WT90
52
WT95
Number of operating hours in the actuating range
WT95
12.2.3

Meaning of diagnostics values

1 STRKS - stroke number
The movements of the actuator in operation are summed up and can be read here as the
stroke number. Unit: 100% strokes, i.e. the path between 0 and 100 % and back. The value
is written in a non-volatile memory every 15 minutes. It can be set to zero using the
increment button.
2 CHDIR - number of changes of direction
Every change of direction of the actuator caused in the dead zone is noted in the closed-loop
controller and added to the number of changes of direction.
The value is written in a non-volatile memory every 15 minutes. It can be set to zero using
the
3 CNT - number of fault messages
Every fault is noted in the closed-loop controller and added to the number of fault messages.
The counter can be set to zero using the
4 A1CNT - number of alarms 1
and
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
increment button.
Alarm, fault and system messages
Values that can
be displayed
0 ... 4.29E9
0 ... 4.29E9
0 ... 4.29E9
0 ... 4.29E9
0 ... 4.29E9
0 ... 4.29E9
0 ... 4.29E9
increment button.
12.2 Diagnostics
Unit
Reset
possibl
e
Hours
X
Hours
X
Hours
X
Hours
X
Hours
X
Hours
X
Hours
X
225