Diagnostics Messages In Case Of Deactivated Condensed Status - Siemens SIPART PS2 PA 6DR55 Series Operating Instructions Manual

Electropneumatic positioner
Table of Contents

Advertisement

11.3.4.1

Diagnostics messages in case of deactivated condensed status

The diagnostics messages of the DIAGNOSTICS physical block parameter in case of the
deactivated condensed status are shown in the following table:
Byte
Bit
Name and meaning
0
0 ... 2
Not used
3
DIA_TEMP_ELECTR
Electronic unit temperature too
high
4
DIA_MEM_CHKSUM
Memory error
5
Not used
6
DIA_NOT_INIT
Device not initialized
7
DIA_INIT_ERR
Error in initialization
1
0
DIA_ZERO_ERR
Lower end stop beyond the
tolerance
1
DIA_SUPPLY
Error in the compressed air
supply
2
Not used
3
DIA_WARMSTART
Warm restart executed (goes to
"0" after 10 s)
4
DIA_COLDSTART
Restart executed
(goes to "0" after 10 s)
5
DIA_MAINTENANCE
Maintenance required
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
Functions/operations using PROFIBUS PA
Cause
-
The temperature measured at
the device electronic unit has
exceeded one or more set
thresholds.
During operation, the memory is
constantly checked for the
checksum and write/read errors.
This message is generated in
case of an error.
-
The initialization process
required for the device
functioning has not yet been
carried out successfully.
Values obtained during the
initialization process cannot be
used.
The lower end stop is beyond the
set tolerance.
A run time overshoot was
detected. In all probability, the
energy (compressed air) is not
available.
-
Power was fed to the device.
SIMATIC PDM was used to
trigger a warm restart.
The internal watchdog has
responded.
The device was reset to factory
settings.
To determine the cause, check in
DIAGNOSTICS_EXTENSION
and
DIAGNOSTICS_EXTENSION_2
which diagnostics event has
triggered the message.
11.3 Cyclic data transfer
Measure
-
Check why the temperature is
beyond the specified range.
Replace the electronic unit.
-
Carry out the device initialization
process.
Carry out the device initialization
process again. Check the
relevant parameter settings.
Check the valve. Flow restrictors
and/or the seat ring are probably
worn out.
Establish the compressed air
supply and check the feed lines.
-
Check the cabling and the supply
unit.
-
Depends on the triggering
diagnostics event.
205