Commissioning
9.4 Commissioning the part-turn actuators
5. Start the initialization process. Keep the
following is shown on the digital display:
Note
The positioner runs through five initialization steps during the automatic initialization
process. Displays for the initialization steps from "RUN1" to "RUN5" are shown in the
lower line on the digital display. The initialization process depends on the actuator used,
and takes up to 15 minutes.
6. The following display indicates that the automatic initialization is complete. The total
angle of rotation of the actuator is shown on the upper line on the digital display:
Aborting the automatic initialization process
1. Press the
2. Exit the Configuration mode. Keep the
5 s.
3. The software status is displayed.
4. After releasing the
i.e. the part-turn actuator has not been initialized.
9.4.3

Manual initialization of part-turn actuators

You can use this function to initialize the positioner without needing to move the actuator to
the end stops. The start and end positions of the actuator travel are set manually. When the
control parameters are optimized, the further initialization process runs automatically.
Conditions
The following conditions must be fulfilled before activating the manual initialization:
1. The positioner has been prepared for using on linear actuators.
2. The actuator can be moved completely.
130
operating mode button. The following is shown on the digital display:
operating mode button, the positioner is in the "P manual mode",
button pressed for more than 5 s until the
operating modes button pressed for more than
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07