Manual Initialization Of Linear Actuators - Siemens SIPART PS2 PA 6DR55 Series Operating Instructions Manual

Electropneumatic positioner
Table of Contents

Advertisement

Setting parameter 3
Proceed as follows to set parameter 3:
1. On the scale of the lever, read the value marked by the carrier pin.
2. Set the parameter to the read value. Use the
Aborting the automatic initialization process
1. Press the
2. Exit the "Configuration" mode. Keep the
3. The software status is displayed.
4. After releasing the
9.3.3

Manual initialization of linear actuators

You can use this function to initialize the positioner without needing to move the actuator to
the end stops. The start and end positions of the actuator travel are set manually. When the
control parameters are optimized, the further initialization process runs automatically.
Conditions
The following conditions must be fulfilled before activating the manual initialization:
1. The positioner has been prepared for using on linear actuators.
2. The actuator spindle can be moved completely.
3. The displayed potentiometer position is within the permissible range between "P5.0" and
Initializing the positioner manually
1. Switch to the "Configuration" mode. Keep the
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
this purpose.
operating mode button. The following is shown on the digital display:
than 5 s.
operating mode button, the positioner is in the "P manual mode",
i.e. the positioner has not been initialized.
"P95.0".
more than 5 s. The following is shown on the digital display:
9.3 Commissioning the linear actuators
increment or
decrement buttons for
operating modes button pressed for more
operating modes button pressed for
Commissioning
125