12.8.8.3

Certificates, approvals, explosion protection for external position detection system

Electrical data
For connecting to circuits with the follow-
ing peak values
Certificates and approvals
CE conformity
Explosion protection
Explosion protection in accordance with
Intrinsic safety "ia"
Intrinsic safety "ic"
Non-sparking "nA"
Permissible ambient temperature
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
U
= 5 V
i
I
= 100 mA
i
P
= 160 mW
i
C
= negligibly small
i
L
= negligibly small
i
The applicable directives and applied standards with their revision levels can
be found in the EC declaration of conformity on the Internet.
Ex markings
ATEX
Zone 1:
II 2 G Ex ia IIC T6/T4 Gb
Zone 21:
II 2 D Ex ia IIIC T110°C Db
Zone 2:
II 3 G Ex ic IIC T6/T4 Gc
Zone 2:
II 3 G Ex nA IIC T6/T4 Gc
T4: -40 ... +90 °C (-40 ... +194 °F)
T6: -40 ... +60 °C (-40 ... +140 °F)
Technical data
12.8 Option modules