10.2.4.24

Diagnostic value '30.TEMP - Current temperature'

Display range:
Purpose:
10.2.4.25
Diagnostic value '31.TMIN - Minimum temperature' / '32.TMAX - Maximum
temperature'
Display range:
Purpose:
10.2.4.26
Diagnostic value '33.T1' ... '41.T9' - Number of operating hours in the temperature

range 1 to 9

Display range:
Purpose:
Temperature range [°C]
Operating hours in temperature ranges T1 to T2
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
°C: -50 ... 100
°F: -58 ... 212
Current temperature in the positioner enclosure. The sensor is pre-
sent on the basic electronics. In order to switch over the tempera-
ture display between °C and °F, press the
°C: -50 ... 100
°F: -58 ... 212
The minimum and maximum temperatures within the enclosure are
constantly determined and saved as with a slave pointer. This
value can only be reset in the factory.
In order to switch over the temperature display between °C and °F,
press the
button.
0 ... 4.29E9
Statistics about the duration of operation in different temperature
ranges is maintained in the device. An average of the measured
temperature is taken every hour and the counter assigned to the
corresponding temperature range is incremented. This helps in
drawing conclusions about the past operating conditions of the
device and the entire control valve.
The temperature ranges are classified as follows:
T1
T2
T3
-
≥ -30
≥ -15
≤ -30
< -15
< 0
Alarm, error, and system messages
T4
T5
T6
≥ 0
≥ 15
≥ 30
< 15
< 30
< 45
10.2 Diagnostics
button.
T7
T8
T9
≥ 45
≥ 60
≥ 75
< 60
< 75
-
221