Purpose:
Description:
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
You can use this diagnostics parameter to read the last test result
or start an offline leakage test with which you can detect leakages
in the actuator or in the pipe installation. Display is percent stroke
per minute referred to the total stroke. A test result originates from
one of the following options:
• Function '11.LEAK' has already been carried out.
• Leakage test was already carried out during initialization, see
procedure of RUN3 in section Sequence of automatic
initialization (Page 117).
• 'Offline leakage test' function was already executed by a HOST
system.
"-" in the display can have the following causes:
• A leakage test has not yet been carried out.
• Resetting to the factory settings was carried out using the
''50.PRST' Preset (Page 173) > ALL' parameter.
• Positioner is not initialized.
How to start the test
1. Move the actuator to the position at which you wish to start the
Recommendation:
test.
in the center position.
2. In 'Diagnostics' mode, go to the '11.LEAK' diagnostic value as
described in section Display of diagnostics values (Page 207).
3. Start the function by pressing the
seconds.
'Strt' is output in the display. The function is started after 5 sec-
onds. 'tESt' and the current position of the actuator (actual value)
are then displayed alternately for one minute.
After one minute, the display shows the difference in the actuator
position before and after the test. This means: the actuator position
has changed by the displayed value in one minute.
Alarm, error, and system messages
Set value to approx. 50. The actuator is
button for at least 5
10.2 Diagnostics