Alarm, error, and system messages
10.1 Output of system messages in the display
Message
Line
Up
Down
U->d
X
NOZZL
X
TESt
X
LEAKG
X
nn.n
X
%/MIN
X
nn.n
X
FINISH
X
See also
System messages before initialization (Page 201)
204
Meaning/cause
Actuator stops (the initialization process was
interrupted using the "-" button when the
actuation speed display was active)
Leakage test active (the "+" button was
pressed when the actuation speed display
was active)
Value and unit of the result after the leakage
test
Initialization completed successfully with the
display of actuator travel or the actuator
angle
Measure
RUN4.
To change the travel time, interrupt the
initialization process using the
Activate the leakage test using the
key.
1. The travel time can be changed by ad-
justing the restrictor(s).
2. Redetermine the positioning speed using
the
key.
3. Continue using
key.
Wait for one minute.
Rectify the leakage if the value is too
large.
Continue using
key.
1. Briefly acknowledge using
2. Leave configuration level by long press-
ing of
key.
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB