Monitoring the high limit temperature 'J.\\TMAX'

J. TMAX - Monitoring the upper limit temperature
Requirement:
Possible settings:
Purpose:
Factory setting:
J1.TUNIT - temperature unit
Possible settings:
Purpose:
Factory setting:
J2.LEVL1 - threshold 1
Adjustment range:
Purpose:
Factory setting:
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
The '52.XDIAG' Activating for extended diagnostics (Page 174)
parameter is set to 'On1', 'On2' or 'On3'.
• OFF
• On
The current temperature inside the enclosure of the field device is
recorded by a sensor on the basic electronics. Use this parameter
to activate continuous monitoring of the high limit temperature
inside the enclosure. Monitoring is performed in three steps. To
activate monitoring, set the parameter to 'On'. Sub-parameters are
displayed. Appropriately set the sub-parameters.
The value is displayed in Diagnostic value '31.TMIN - Minimum
temperature' / '32.TMAX - Maximum temperature' (Page 221). The
positioner triggers a message if the current value exceeds one of
the three thresholds.
OFF
°C
°F
Use this sub-parameter to set the temperature unit '°C' or '°F'. The
selected temperature unit is then also applicable for all other tem-
perature-based parameters.
°C
-40.0C ... 90.0C
-40.0F ... 194.0F
Use this sub-parameter to set the temperature for threshold 1.
The positioner triggers a message if the current temperature inside
the enclosure overshoots threshold 1. The process to activate and
display this message is described in the 'XDIAG' parameter.
75.0C