Parameter assignment
9.4 Description of parameters
H1.TUNIT - temperature unit
Possible settings:
Purpose:
Factory setting:
H2.LEVL1 - threshold 1
Adjustment range:
Purpose:
Factory setting:
H3.LEVL2 - threshold 2
Adjustment range:
Purpose:
Factory setting:
H4.LEVL3 - threshold 3
Adjustment range:
Purpose:
Factory setting:
See also
'39.YCLS' Tight closing with manipulated variable (Page 166)
192
°C
°F
Use this sub-parameter to set the temperature unit '°C' or '°F'. The
selected temperature unit is then also applicable for all other tem-
perature-based parameters.
°C
-40.0C ... 90.0C
-40.0F ... 194.0F
Use this sub-parameter to set the temperature for threshold 1.
The positioner triggers a message if the current temperature inside
the enclosure undershoots threshold 1. The process to activate
and display this message is described in the 'XDIAG' parameter.
-25.0C
-40.0C ... 90.0C
-40.0F ... 194.0F
Use this sub-parameter to set the temperature for threshold 2.
The positioner triggers a message if the current temperature inside
the enclosure undershoots threshold 2. The process to activate
and display this message is described in the 'XDIAG' parameter.
-30.0C
-40.0C ... 90.0C
-40.0F ... 194.0F
Use this sub-parameter to set the temperature for threshold 3.
The positioner triggers a message if the current temperature inside
the enclosure undershoots threshold 3. The process to activate
and display this message is described in the 'XDIAG' parameter.
-40.0C
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB