Monitoring the stiction (slipstick) 'd.\\STIC'
d. STIC - Monitoring the stiction (slipstick)
Requirement:
Possible settings:
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
0.1 ... 100.0
Use this sub-parameter to set the factor for formation of threshold
1. Set the factor in a range from '0.1' to '100.0'. The threshold is
the product of 'C1.LIMIT' and 'C2.FACT1'.
The threshold 1 message is displayed when threshold 1 is ex-
ceeded. The process to activate and display this message is de-
scribed in the 'XDIAG' parameter.
1.0
0.1 ... 100.0
Use this sub-parameter to set the factor for formation of threshold
2. Set the factor in a range from '0.1' to '100.0'. The threshold is
the product of 'C1.LIMIT' and 'C3.FACT2'.
The threshold 2 message is displayed when threshold 2 is ex-
ceeded. The process to activate and display this message is de-
scribed in the 'XDIAG' parameter.
1.5
0.1 ... 100.0
Use this sub-parameter to set the factor for formation of threshold
3. Set the factor in a range from '0.1' to '100.0'. The threshold is
the product of 'C1.LIMIT' and 'C4.FACT3'.
The threshold 3 message is displayed when threshold 3 is ex-
ceeded. The process to activate and display this message is de-
scribed in the 'XDIAG' parameter.
2.0
The '52.XDIAG' Activating for extended diagnostics (Page 174)
parameter is set to 'On1', 'On2' or 'On3'.