50.Prst' Preset - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with and without hart
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

9.4.2.19

'50.PRST' Preset

Possible settings:
Purpose:
Description:
Factory setting:
See also
Display of diagnostics values (Page 207)
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
• ALL
• Init
• PArA
• diAg
Use this parameter to restore the factory settings for most parame-
ters. The following parameter groups are available:
• ALL: Reset all parameters together which can be reset by 'Init',
'PArA' and 'diAg'.
• Init: Reset initialization parameters '1.YFCT' to '5.INITM'.
• PArA: Reset application parameters '6.SCUR' Current range of
setpoint (Page 159) to '49.\\LIM' Response threshold of fault
message 'Control deviation' (Page 172).
• diAg: Reset parameters A to P of the extended diagnostics as
well as parameter '52.XDIAG' Activating for extended
diagnostics (Page 174).
An overview of the parameters and factory settings can be found in
section Tabular overview of the parameters (Page 147).
In order to select one of the parameter groups listed above, repeat-
edly press the
button until the desired setting is output in the
display. Start the function by keeping the
'oCAY' is output in the display. The values of the parameter group
are now the factory settings.
If you wish to use a previously initialized positioner on a different
control valve, set the parameters to the factory settings prior to a
new initialization. To do this, use the 'ALL' or 'Init' setting.
Restore the factory settings if you have changed several parame-
ters at once without being able to predict their effect and the unde-
sired reactions which may occur as a result. To do this, use the
'ALL' setting.
ALL
Parameter assignment
9.4 Description of parameters
button pressed until
173