Parameter assignment
9.4 Description of parameters
9.4.2.15

'45.A1' / '46.A2' Response threshold of alarms

Adjustment range:
Purpose:
Factory setting:
170
0.0 ... 100.0
These parameters are used to specify when an alarm should be
displayed. The response thresholds of the alarms (in percent) refer
to the MPOS scale in the "'37.YNRM' Standardization of manipu-
lated variable (Page 164)" parameter. The MPOS scale corre-
sponds to the mechanical travel.
Depending on the setting of the alarm function in the "'44.AFCT'
Alarm function (Page 168)" parameter, the alarm is triggered upon
an upward violation (Max) or downward violation (Min) of this re-
sponse threshold.
With "A1": 10.0
With "A2": 90.0
SIPART PS2 with and without HART