Parameter assignment

9.1

Introduction to parameter assignment section

A positioner is responsible for controlling a valve and for monitoring the status of a valve.
The parameters described in this section are used to optimally adapt the positioner to the
valve and its application.
The parameters are divided into initialization parameters, application parameters, and the
extended diagnostics parameters.
● Initialization parameters 1 to 5 (Page 155): Describes die parameters which are relevant
● Application parameters 6 to 52 (Page 159): Describes die parameters with which the
● Extended diagnostics parameters A to P (Page 176): Describes the diagnostics functions
The following configuration schematic shows the principle of operation of the parameters.
This is followed by a tabular overview of the parameters. Finally, the individual parameters
and their functionality are described.
Furthermore, the positioners with HART, PA and FF communication interface in combination
with a host system, e.g. SIMATIC PDM or HART communicator etc., offer the following
advantages:
● Offline tests such as full stroke test, step response test, multi-step response test and
● Diagnostics cockpit which provides an overview of the state of positioner and valve.
● Logbook with time stamp for documentation of all events such as the violation of
● Wizards which provide prompting through the relevant parameters during commissioning,
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
for initial commissioning of the positioner on the valve. For example, you can start the
automatic initialization here.
positioner is adapted to the valve application, for example tight closing at the end stops.
which are provided by the positioner. These include monitoring of leakages as well as the
partial stroke test. Following activation of these functions, the positioner continuously
monitors the status of the valve. If you enter thresholds in the parameters of the
diagnostics functions, the positioner actively signals high or low violation of these
thresholds. The current monitoring state for these thresholds is displayed as a diagnostic
value. For additional details on diagnostics and diagnostic values, refer to the section
Diagnostics (Page 207).
valve performance test.
thresholds.
the partial stroke test as well as the offline test.