4. Call the "INITM" parameter. To do this, press the
5. Start the initialization process. Press the
6. The current potentiometer position is output on the display after 5 seconds:
7. Determine the lower endstop of the actuator.
8. Move the actuator to the desired position using the
9. Press the
10.Determine the upper endstop of the actuator. Move the actuator to the desired position
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
following:
shows the following:
button. The current position of the actuator is applied. The display shows
the following:
Note
Fault message "RANGE"
The selected end position is beyond the permissible measuring range if the "RANGE"
message is output on the display. Correct the settings as follows:
1. Move the friction clutch until the display shows "OK".
2. Press the
button.
3. Move the actuator to another position using the
4. Abort the manual initialization process by pressing the
5. Then return to "P manual mode".
6. Correct the actuator travel and the position detection.
using the
or
button.
7.6 Commissioning part-turn actuators
button twice. The display shows the
button for at least 5 seconds until the display
or
button.
or
button.
button.
Commissioning
135