5. Start the initialization process. To do this, press the
6. The following display indicates that the automatic initialization is complete. The total angle
Aborting the automatic initialization process
1. Press the
2. Exit the "Configuration" mode. To do this, press the
See also
Sequence of automatic initialization (Page 117)
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
the display shows the following:
The positioner runs through five initialization steps during the automatic initialization
process. Displays for the initialization steps from "RUN1" to "RUN5" are shown in the
lower line on the display. The initialization process depends on the actuator used, and
takes up to 15 minutes.
of rotation of the actuator is shown on the upper line on the display:
button. The display shows the following:
The positioner is in the "Configuration" mode.
The software status is displayed.
After releasing the
is not initialized.
button, the positioner is in "P manual mode". The part-turn actuator
7.6 Commissioning part-turn actuators
button for at least 5 seconds until
button for at least 5 seconds.
Commissioning