Commissioning
7.6 Commissioning part-turn actuators
7.6.2

Automatic initialization of part-turn actuators

Requirements
The following conditions must be fulfilled before activating the automatic initialization:
1. The travel range of the actuator can be passed through completely.
2. The actuator shaft is at a central position.
Initializing the part-turn actuator automatically
Note
Interrupting initialization
An ongoing initialization can be interrupted at any time. To do this, press
configured until then are retained.
All parameters are reset to factory settings only if you have explicitly activated the preset
settings in the "PRST" parameter.
1. Switch to the "Configuration" mode. To do this, press the
until the display shows the following:
2. Use the
shows the following:
3. Call the "2.YAGL" parameter. To do this, briefly press the
already been set to 90° automatically. The display shows the following:
4. Call the "4.INITA" parameter. To do this, briefly press the
the following:
132
button to change from linear actuator to part-turn actuator until the display
button for at least 5 seconds
button. This parameter has
button. The display shows
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB