Manual Initialization Of Linear Actuators - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with and without hart
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Aborting the automatic initialization process
1. Press the
2. Exit the "Configuration" mode. To do this, press the
See also
Sequence of automatic initialization (Page 117)
7.5.3

Manual initialization of linear actuators

You can use this function to initialize the positioner without needing to move the actuator to
the lower and upper endstops. The lower and upper endstops of the actuator travel are set
manually. When the control parameters are optimized, the further initialization process runs
automatically.
Requirements
The following requirements must be fulfilled before activating manual initialization:
1. The positioner has been prepared for using on linear actuators.
2. The actuator spindle can be moved completely.
3. The displayed potentiometer position is within the permissible range between "P5.0" and
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
button. The display shows the following:
The positioner is in the "Configuration" mode.
The software status is displayed.
After releasing the
initialized.
"P95.0".
button, the positioner is in "P manual mode". The positioner is not
Commissioning
7.5 Commissioning linear actuators
button for at least 5 seconds.
127