1.14 SEPARATOR KIT INSTALLATION.

Type C configuration, sealed chamber and
fan assisted.
Separator kit Ø 80/80.
is kit allows air to come
in from outside the building and the fumes to exit
from the chimney or ue through divided ue
exhaust and air intake pipes. Combustion prod-
ucts are expelled from pipe (S) (in plastic, so as
to resist acid condensate). Air is taken in through
duct (A) for combustion (this is also in plastic).
e intake pipe (A) can be installed either on the
right or le hand side of the central exhaust pipe
(S). Both ducts can be routed in any direction.
• Kit assembly (Fig. 1-20): install ange (4) on
the central hole of the boiler, positioning gasket
(1) with the circular projections downwards
in contact with the boiler ange, and tighten
using the hex screws with at tip contained in
the kit. Remove the at ange present in the
lateral hole with respect to the central one (ac-
cording to needs) and replace it with the ange
(3), positioning the gasket (2) already present in
9
5
S
7
4
1
* to er complete C
terminal.
the boiler and tighten using the supplied self-
threading screws. Fit the male end (smooth) to
the bends (5) in the female end of the anges
(3 and 4). Fit the intake terminal (6) with the
male side (smooth) in the female side of the
bend (5) up to the end stop, ensuring that the
internal and external wall sealing plates are
tted. Fit the exhaust pipe (9) with the male
side (smooth) to the female side of the bend
(5) up to the end stop; making sure that the
internal wall sealing plate has been tted, this
will ensure sealing and joining of the elements
making up the kit.
• Installation clearances (Fig. 1-21).
mum installation clearance measurements of
the Ø 80/80 separator terminal kit have been
stated in some limit conditions.
• Extensions for separator kit Ø 80/80. The
maximum vertical straight length (without
bends) that can be used for Ø 80 intake and
exhaust pipes is 41 metres, regardless from
whether they are used for intake or exhaust.
5
6
7
8
A
3
2
e kit includes:
N° 1 - Exhaust gasket (1)
N° 1 - Flange seal gasket (2)
N° 1 - Female intake ange (3)
N° 1 - Female drain ange (4)
N° 2 - Bend 90° Ø 80 (5)
N° 1 - Intake terminal Ø 80 (6)
N° 2 - Internal wall sealing plates (7)
N° 1 - External wall sealing plate (8)
N° 1 - Drain pipe Ø 80 (9)
con guration also provide for a roof discharge
53
minimum slope 1.5%
bend in suction and in exhaust) that can be
used for Ø 80 intake and exhaust pipes is 36
metres, regardless from whether they are used
for intake or exhaust.
N.B.: to favour the removal of possible conden-
sate forming in the exhaust pipe, tilt the pipes
towards the boiler with a minimum slope of
1.5% (Fig. 1-22).
e mini-
C
* - C
53
83
1-20
14
e maximum horizontal straight length (with
C
43
1-21
C
83
1-22