Input
Recommended Maximum DC
Power (Module STC)
Transformer-less, Ungrounded
Maximum Input Voltage
Nominal DC Input Voltage
Maximum Input Current
Reverse-Polarity Protection
Ground-Fault Isolation Detection
Maximum Inverter Efficiency
European Weighted Efficiency
Nighttime Power Consumption
Additional Features
Supported Communication
Interfaces
Standards Compliance
Safety
Grid Connection Standards
Emissions
WEEE, RoHS
Installation Specifications
AC Output
DC Input
Maximum Installation Height
Dimensions (W x L x H)
Weight
Operating Temperature Range
Cooling
Protection Rating
Bracket Mounted (Bracket Provided)
* For inverter power de-rating refer to the application note at the following link:
temperature-derating-note.pdf
SolarEdge Installation Guide – MAN-01-00057-2.0
SE7k
SE8k
7700
8800
12
97.7
RS485, RS232, Ethernet, Zigbee (optional)
IEC-62103 (EN50178), Draft IEC-62109, UL1741
VDE-AR-N-4105, VDE 0126-1-1, AS-4777,
RD-1663, DK 5940, IEEE1547, NEC
IEC61000-6-2, IEC61000-6-3, IEC61000-3-11,
IEC61000-3-12, FCC part15 class B
Technical Specifications
SE9k
SE10k SE12.5k
9900
11000
Yes
950
750
13.5
15
16.5
Yes
600 kΩ Sensitivity
98
97.6
97.6
97.5
< 2.5
Yes
Cable Gland - diameter 11-17
MC4
2000
540 x 315 x 260
32
-20 – +60*
Fan (user replaceable)
IP65 – Outdoor and Indoor
http://www.solaredge.com/files/pdfs/se-
88
SE15k
13000
13700
W
Vdc
Vdc
21
22
Adc
%
97.4
97.4
%
W
mm
m
mm
kg
°C