Connecting the AC Wires: Strip off the isolation and expose the wires in
the AC cable, as follows:
Single phase inverters – three wires:
Protective Earth (PE) wire
Neutral (N)
Line 1 (L)
Three phase inverters – five wires:
Protective Earth (PE) wire
Neutral (N)
Line 1 (L)
Line 2 (L)
Line 3 (L)
The lengths of the wires to strip are as follows:
Figure 11: Wire Lengths to Strip
Strip 8 mm for contact.
Individual cable length 50 mm.
WARNING!
Make sure to connect the PE (ground) connector first.
7
Insert the cable through the AC cable gland on the right and connect the wires
to the appropriate terminal connectors according to their labels: PE, L and N in
the single phase inverter, PE, L1, L2, L3 and N in the three phase inverter.
Figure 12: Inserting the Cable
Figure 12: Inserting the Cable Through the AC Cable Gland – Single Phase Inverter
Through the AC Cable Gland –
Figure 13: Inserting the Cable Through the AC Cable Gland – Three Phase Inverter
Single Phase Inverter
SolarEdge Installation Guide – MAN-01-00057-2.0
Installing the Inverter
50mm
8mm
Figure 13: Inserting the Cable
Through the AC Cable Gland –
Three Phase Inverter