Connecting the Inverter

Inverter Connection Overview

The SolarEdge inverter can be configured in the field for an AC grid, including
AC voltage and frequency. If the inverter's default settings are not suited to the
country of the installation site, then please refer to page 72 for a description of
how to configure the inverter for the required country.
With the SolarEdge Configuration Tool, you can configure the inverter's AC
settings to different settings than those provided by default for the country of the
installation site, or perform other modifications. A full description of the
Configuration Tool is provided in the SolarEdge Configuration Tool Software
Guide.
Refer to the following table to determine the correct fuse size to use at the
connection point of the SolarEdge inverter to the grid:
Inverter
SE3000
SE3500
SE4000
SE4000-16A
SE5000
SE6000
SE7k
SE8k
SE9k
SE10k
SE12.5k
NOTE
For more wiring information, you may refer to the Application Note called SolarEdge
Recommended AC Wiring, which can be accessed from the SolarEdge website.
NOTE
You should also refer to the technical specifications in Appendix B, Technical
Specifications on page 85. Pay special attention to the inverter specifications because
they may differ slightly in different countries.
SolarEdge Installation Guide – MAN-01-00057-2.0
Maximum Output Current
16.5 A
19.5 A
22 A
16 A
27 A
27 A
11.5 A
13.5 A
15.5 A
17.5 A
19.5 A
Installing the Inverter
Suggested Fuse
20 A
25 A
25 A
20 A
32 A
32 A
16 A
16 A
20 A
20 A
25 A
25