SolarEdge storedge Installation Manual page 49

Hide thumbs Also See for storedge:
Table of Contents

Advertisement

Step 2: Pairing Power Optimizers to the Inverter
Keep holding for 5 seconds until the following is displayed:
P a i r i n g
T u r n
 2.  Turn the inverter ON/OFF switch to ON within 5 seconds. If you wait longer than 5 seconds the 
inverter exits the pairing mode. The following message is displayed indicating that the inverter is 
performing the pairing:
P a i r i n g
R e m a i n i n g
 3.  Wait for the completion of the pairing (remaining seconds is 0). If pairing fails, an error is displayed. In 
this case, repeat the pairing steps, and refer to Power Optimizer Troubleshooting  on page 90. If the 
problem persists, contact SolarEdge Support. When pairing succeeds, the following message is 
displayed:
P a i r i n g
P a i r i n g
 
The system startup process begins:
Since the inverter is ON, the power optimizers start producing power and the inverter starts converting 
AC.
WARNING!
When you turn ON the inverter ON/OFF switch, the DC cables carry a high voltage and the power
optimizers no longer output a safe 1V output.
Après avoir mis l'interrupteur ON/OFF de l'onduleur monophasé sur ON, les câbles DC portent une
haute tension et les optimiseurs de puissance ne génèrent plus la tension de sécurité de 1V.
When the inverter starts converting power after the initial connection to the AC, the inverter enters 
Standby mode until its working voltage is reached. This mode is indicated by the flickering green inverter 
LED.
While the inverter is in Standby mode, it monitors the grid and verifies correct grid voltage and 
frequency. The following message is displayed:
W a k i n g
R e m a i n i n g :
The countdown indicates the seconds remaining until entering the Production mode. This time is in 
accordance with local regulations and is typically between three to five minutes. 
When countdown is complete, the inverter enters Production mode and produces power. The steadily 
lit green inverter LED indicates this mode.
 4.  Enable Rapid Shutdown:
 a.  Enter Setup mode as described in Configuring the Inverter Using the LCD Light Button on page 55.
 b.  Scroll to the   M aintenance menu and select Optimizer Conf.   è Set Rapid Shutdown è Enable.
S e t
R a p i d
E x i t
48
S w i t c h
T o
O n
[ s e c ] : 1 8 0
C o m p l e t e d
U p . . .
0 5 1
S e c
S h u t d o w n
SolarEdge StorEdge Installation Guide MAN-01-000262-1.2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents