9V Battery Replacement - SolarEdge storedge Installation Manual

Hide thumbs Also See for storedge:
Table of Contents

Advertisement

NOTE
If you remove the old inverter and do not immediately install a new one, then:
Lock the StorEdge Connection Unit in the OFF position using a lock on the switch.
o
Use insulation tape to isolate each of the AC and DC wires.
o
Seal the open conduits using duct tape.
o
 11.  Place the new inverter on the mounting bracket; insert the screws securing the inverter to the 
mounting bracket. 
 12.  Screw the two conduit nuts in the inverter securing the StorEdge Connection Unit to the inverter. 
 13.  Connect the DC and AC wires to the inverter. 
 14.  Place the ferrite beads on the wires and close them. Make sure the DC labeled ferrite bead is placed on 
the DC wires and the AC labeled ferrite bead is placed on the AC wires.    
 15.  Close the inverter cover.
 16.  Configure the system to the required application as described in System Configuration on page 78
 17.  Perform the commissioning steps as described in Commissioning the Installation on page 44.

9V Battery Replacement

If Warning 8: Connection Unit Low 9V Battery is displayed in the main status screen, replace the 9V 
battery in the StorEdge Connection Unit.
 1.  Turn OFF the inverter ON/OFF switch, and wait until the LCD indicates that the DC voltage is safe 
(<50V), or wait five minutes before continuing to the next step.
WARNING!
If you cannot see the inverter panel, or if a malfunction is indicated on the LCD panel, wait five
minutes for the input capacitors of the inverter to discharge.
Si vous ne pouvez pas voir l'écran de l'onduleur ou si un dysfonctionnement est indiqué sur
l'écran LCD, attendez cinq minutes pour que les condensateurs d'entrée de l'onduleur soient
déchargés.
 2.  Turn OFF the StorEdge Connection Unit and the AC switch of the distribution panel. 
 3.  Open and remove the StorEdge Connection Unit cover.
 4.  Open and remove the transparent internal cover.
 5.  Remove the battery from the upper board of the StorEdge Connection Unit and replace with a new 
standard 9V battery.
 6.  Close the StorEdge Connection Unit covers.
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.2
Appendix C: Replacing and Adding System Components
Figure 46: The battery holder