Electrical Notes - York YLUA Series Operation Manual

Air-cooled scroll compressor condensing units
Table of Contents

Advertisement

Electrical Notes

NOTES:
1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the
rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If the optional Factory Mounted
Control Transformer is provided, add the following MCA values to the electrical tables for the system providing power
to the transformer: -17, add 2.5 amps; -28, add 2.3 amps; -40, add 1.5 amps, -46, add 1.3 amps; -58, add 1 amps.
2. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included in
the circuit, per N.E.C. Article 440.
3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load
amps for all other loads included in the circuit to avoid nuisance trips at start-up due to lock rotor amps. It is not rec-
ommended in applications where brown outs, frequent starting and stopping of the unit, and/or operation at ambient
temperatures in excess of 95ºF (35ºC) is anticipated.
4. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated load
amps for all other loads included in the circuit, per N.E.C. Article 440-22.
5. Circuit breakers must be UL listed and CSA certified and maximum size is based on 225% of the rated load amps for
the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Otherwise, HACR-type
circuit breakers must be used. Maximum HACR circuit breaker rating is based on 225% of the rated load amps for
the largest motor plus 100% of the rated load amps for all other loads included in the circuit.
6. The "INCOMING WIRE RANGE" is the minimum and maximum wire size that can be accommodated by the unit wir-
ing lugs. The (2) preceding the wire range indicates the number of termination points available per phase of the wire
range specified. Actual wire size and number of wires per phase must be determined based on the National Electrical
Code, using copper connectors only. Field wiring must also comply with local codes.
7. A ground lug is provided for each compressor system to accommodate a field grounding conductor per N.E.C.
Table 250-95. A control circuit grounding lug is also supplied.
8. The supplied disconnect is a "Disconnecting Means" as defined in the N.E.C. 100, and is intended for isolating the
unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not intended to
be a Load Break Device.
9. Field Wiring by others which complies to the National Electrical Code & Local Codes.
LEGEND
ACR-LINE
C.B.
D.E.
DISC SW
FACT MOUNT CB
FLA
HZ
MAX
MCA
MIN
MIN NF
RLA
S.P. WIRE
UNIT MTD SERV SW
LRA
JOHNSON CONTROLS
ACROSS THE LINE START
CIRCUIT BREAKER
DUAL ELEMENT FUSE
DISCONNECT SWITCH
FACTORY MOUNTED CIRCUIT BREAKER
FULL LOAD AMPS
HERTZ
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MINIMUM
MINIMUM NON FUSED
RATED LOAD AMPS
SINGLE POINT WIRING
UNIT MOUNTED SERVICE (NON-FUSED DISCONNECT
SWITCH)
LOCKED ROTOR AMPS
FORM 150.63-EG4 (1012)
VOLTAGE CODE
50 = 380/415-3-50
33

Advertisement

Table of Contents
loading

Table of Contents