Wiring Lugs (Cont'd)
GLOBAL MARKET
YLAA
VOLTS
208
230
0100/0101
380
460
575
208
230
0120/0130/0125
380
400/460
575
208
230
0135/0141
380
400/460
575
208
230
0136/0142
380
400/460
575
208
230
0150/0155/0158/
380
0156
400/460
575
208
230
0170/0175
380
460
575
NOTE: A lternate lugs are provided in the panel for field electricians and contractors, should there be a need for other lug arrangements that the
installed lugs on the non-fused disconnect switch and circuit breaker panels.
JOHNSON CONTROLS
SINGLE POINT
SUPPLY
TERMINAL
BLOCK
INSTALLED
INSTALLED
HZ
LUG
60
(2) # 6 - 500
(2) 250 - 500
60
(2) # 6 - 500
(2) 250 - 500
60
(1) # 6 - 500
(2) 3/0 - 250
60
(1) # 6 - 500
(2) 3/0 - 250
60
(1) # 6 - 500
(1) 6 - 350
60
(2) # 6 - 500
(3) 2/0 - 400
60
(2) # 6 - 500
(3) 2/0 - 400
60
(1) # 6 - 500
(2) 3/0 - 250
60
(1) # 6 - 500
(2) 3/0 - 250
60
(1) # 6 - 500
(2) 3/0 - 250
60
(2) # 6 - 500
(3) 2/0 - 400
60
(2) # 6 - 500
(3) 2/0 - 400
60
(1) # 6 - 500
(2) 250 - 500
60
(1) # 6 - 500
(1) 250 - 500
60
(1) # 6 - 500
(1) 250 - 500
60
(2) # 6 - 500
(2) 250 - 500
60
60
(2) # 6 - 500
(3) 2/0 - 400
60
(1) # 6 - 500
(1) 250 - 500
60
(1) # 6 - 500
(1) 250 - 500
60
(3) 2/0 - 400
(3) 2/0 - 400
60
(3) 2/0 - 400
(3) 2/0 - 400
60
(2) # 6 - 500
(2) 250 - 500
60
(2) # 6 - 500
(1) 250 - 500
60
(1) # 6 - 500
(2) 3/0 - 250
60
(4) 4/0 - 500
(4) 4/0 - 500
60
(4) 4/0 - 500
(4) 4/0 - 500
60
(2) # 6 - 500
(2) 250 - 500
60
(2) # 6 - 500
(2) 250 - 500
60
(1) # 6 - 500
(2) 3/0 - 250
MOLDED CASE
SWITCH SINGLE
POINT SUPPLY
ALTERNATE
LUG
LUG
(3) 2/0 - 400
(3) 2/0 - 400
(1) 250 - 500
(1) 250 - 500
-
(2) 250 - 500
(2) 250 - 500
(1) 250 - 500
(1) 250 - 500
(1) 250 - 500
(2) 250 - 500
(2) 250 - 500
(3) 2/0 - 400
(2) 3/0 - 250
(2) 3/0 - 250
(3) 2/0 - 400
(2) 250 - 500
(2) 3/0 - 250
(2) 3/0 - 250
(2) 250 - 500
(2) 250 - 500
(3) 2/0 - 400
(2) 3/0 - 250
(1) 250 - 500
-
-
(3) 2/0 - 400
(3) 2/0 - 400
(1) 250 - 500
FORM 150.72-EG6 (516)
MOLDED CASE
CIRCUIT BREAKER
SINGLE POINT SUPPLY
INSTALLED
ALTERNATE
LUG
LUG
(2) 250 - 500
(3) 2/0 - 400
(2) 250 - 500
(3) 2/0 - 400
(2) 3/0 - 250
(1) 250 - 500
(2) 3/0 - 250
(1) 250 - 500
(1) 6 - 350
-
(3) 2/0 - 400
(2) 250 - 500
(3) 2/0 - 400
(2) 250 - 500
(2) 3/0 - 250
(1) 250 - 500
(2) 3/0 - 250
(1) 250 - 500
(2) 3/0 - 250
(1) 250 - 500
(3) 2/0 - 400
(2) 250 - 500
(3) 2/0 - 400
(2) 250 - 500
(2) 3/0 - 250
(1) 250 - 500
(1) 250 - 500
(2) 3/0 - 250
(1) 250 - 500
(2) 3/0 - 250
(2) 250 - 500
(3) 2/0 - 400
(2) 3/0 - 250
(1) 250 - 500
(1) 250 - 500
(2) 3/0 - 250
(1) 250 - 500
(2) 3/0 - 250
(3) 2/0 - 400
(2) 250 - 500
(3) 2/0 - 400
(2) 250 - 500
(2) 250 - 500
(3) 2/0 - 400
(1) 250 - 500
(2) 3/0 - 250
(2) 3/0 - 250
(1) 250 - 500
(3) 2/0 - 400
(2) 250 - 500
(3) 2/0 - 400
(2) 250 - 500
(2) 250 - 500
(3) 2/0 - 400
(2) 3/0 - 250
(1) 250 - 500
(2) 3/0 - 250
(1) 250 - 500
43