STRING:
- visual display of relative humidity (RH%);
- visual display of the outside temperature (with the optional
external probe installed) (TEX);
- cyclic display of relative humidity and outside temperature
(CIC).

10.4 Adjustment parameter management (REGULT).

By pressing the parameter selector you can see the parameters
for adjusting Super CAR operation:
- Adjustment constant (OFFSET), constant adjustable from
-15°C to +15°C which, when the external probe is installed
(optional), changes the standard setting of the delivery
temperature (0°C) (see fig. 19).
Note: if the self-learning function is enabled the Offset
value could be changed automatically.
- The maximum delivery temperature (CH MAX), is the
maximum central heating delivery temperature.
24
EXTERNAL PROBE
Delivery temperature reading correction.
Function of the outside temperature and of the user central
heating temperature setting position.
TM-MAX/MIN = Selected delivery temperature range.
TE = Outside temperature.
Note: if the external probe is installed, by pressing the
push button the maximum delivery temperature is
not set but the Offset value is changed.
Fig. 19