Lennox EL296UHV Installation Instructions Manual page 25

Elite series
Hide thumbs Also See for EL296UHV:
Table of Contents

Advertisement

Maximum Allowable Exhaust Vent Pipe Length (in ft.)Without Insulation In Unconditioned Space For
Winter Design Temperatures Two - Stage High Efficiency Furnace
Winter Design
1
Temperatures
°F (°C)
32 to 21
(0 to -6)
20 to 1
(-7 to -17)
0 to -20
(-18 to -29)
1
Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.
2
Poly-Propylene vent pipe (PP)
NOTE - Maximum uninsulated vent lengths listed may include the termination(vent pipe exterior to the structure) and cannot exceed 5 linear feet or the
maximum allowable intake or exhaust vent length listed in table 5 or 6 which ever is less.
NOTE - If insulation is required in an unconditioned space, it must be located on the pipe closest to the furnace. See figure30.
Vent Pipe
Diameter
045
2
PVC
PP
2 in.
20
18
2-1/2 in.
15
N/A
3 in.
12
10
2 in
12
11
2-1/2 in.
10
N/A
3 in.
6
5
2 in.
8
7
2-1/2 in.
6
N/A
3 in.
2
1
Conditioned
Conditioned
Space
TABLE 7
Unit Input Size
070
090
2
PVC
PP
PVC
30
28
40
22
N/A
30
18
15
25
20
18
25
14
N/A
20
10
8
15
12
11
18
8
N/A
12
6
5
10
Space
Pipe Insulation
Unconditioned
Space
FIGURE 30
Page 25
110
2
2
PP
PVC
PP
PVC
36
24
24
N/A
N/A
40
N/A
N/A
21
32
28
42
22
24
24
N/A
N/A
24
N/A
N/A
12
20
17
22
16
22
20
N/A
N/A
16
N/A
N/A
10
12
11
15
Exhaust
Pipe
Intake
Pipe
135
2
PP
N/A
N/A
37
N/A
N/A
18
N/A
N/A
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents