Check code
5106
Abnormal points and detection methods
Abnormal if TH7 detects to be open/short
Open:−40 or less
Short: 90
or more
TH7: Thermistor <Ambient>
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting
any connectors, or replacing boards.
Check the wiring and connector connection of TH7.
Is there any abnormality such
as a disconnection, looseness or
breakage?
Disconnect the connector to check the
resistance of TH7 using a tester.
Is the detected resistance normal?
Check a temperature of TH7.
Is the detected temperature normal?
OCH576

Ambient thermistor (TH7) open/short

Diagnosis
No
Yes
Yes
Causes and check points
Disconnection or contact failure of connectors
Characteristic defect of thermistor
Defective outdoor multi controller circuit board
The black square (■) indicates a switch position.
Connect the wiring/connector properly.
Yes
Replace it in case of a breakage.
No
The detected temperature of thermistor (TH7)
The detected temperature of TH7 can be displayed by an
can be displayed by an operation of SW1 on the
operation of SW1 on the outdoor multi controller circuit board.
outdoor multi controller circuit board.
SW1 Setting
Display on LED1, 2
ON
−99.9–999.9
OFF
1 2
3
4
5 6 7 8
Replace the outdoor multi controller circuit
board
No
(Malfunction of thermistor circuit).
No abnormality
( A connector contact failure is suspected.)
84
Remedy
Replace the thermistor.
Unit
: