Tile countertopsmayneedtrimcutback3/4"(1,9
cm)fromeachfrontcornerand/orrounded edge
flattened (Figure 7).
311/2'_
(80 cm)
Formed or tile countertop
trimmed 3/4"(1,9 cm) back at
front corners of countertop
Figure 7
opening.
A.G.A./C.G.A.-approved
flexible metallic union-
connected
piping where local codes permit use.
The gas supply
piping can be through
the back wall
(Figure
8, zone
1) or through
the floor
(Figure
8,
zone 2):
Zone 1 - Throughh the Back Wall _
X 6"
- The best place to have your gas line in is
between 1" (2,5 cm) and 8" (20,3 cm) from the floor and
within 3" (7,6 cm) from the center line,
Zone2-ThroughtheFIoor
~2"
51 cm X24"
61
_-
The gas line can also come through
the floor
within 12" (30,5 cm) from the center line against the
back wall,
if the existing
cutout width is greater than 30 1/16"
(76,4 cm), reduce the ¾" (1,9 cm) dimension.
Countertop
must be level. Place a level on the
countertop, first side to side, then front to back. If
the countertop
is not level, the range will not be
level. The oven must be level for satisfactory
baking
results. Cooktop sides of range fit over edges of
countertop opening.
Gas Supply
- Installation
When shipped from the factory, this unit is designed
to operate on 4" (10,16 cm) water column (1,0 kPa)
Natural gas manifold pressure. A convertible
pressure
regulator is connected to the range manifold and
MUST be connected in series with the gas supply line.
To access the regulator, remove the drawer.
For proper operation,
the maximum inlet pressure to
the regulator should be no more than 14" (35,6 cm) of
water column pressure (3,5 kPa).
Figure 8
Seal the openings
Seal any openings in the wall behind the range and
in the floor under the range after gas supply line is
installed.
The inlet pressure to the regulator must be at least
1" (0,25 kPa) greater than the regulator manifold
pressure setting. The regulator is set for 4" (10,2 cm)
water column (1,0 kPa) Natural gas manifold pressure;
the inlet pressure must be at least 5" (12,7 cm) water
column (1,25 kPa) Natural gas. For LP/Propane gas, the
regulator must be set for 10" (25,4 cm) water column
(2,5 kPa) manifold pressure; the inlet pressure must be
at least 11" (27,9 cm) water column (2,75 kPa).
The supply line should be equipped with an approved
shutoff valve (see Figure 11). This valve should be
located in the same room as the range and should be
in a location that allows ease of opening and closing.
Do not block access to the shutoff valve. The valve is
for turning on or shutting off gas to the appliance.
Open the shutoff valve in the gas supply line. Wait a
few minutes for gas to move through the gas line.
Connect
the range to the gas supply
Important:
Remove all packing material and literature
from range before connecting gas and electrical
supply.
To prevent leaks, put pipe joint sealant on all external
pipe threads.
Your regulator is in location as shown in figure 9.
Do not allow regulator to rotate on pipe
when tightening fittings.
Connection
to Pressure
Regulator
The regulator is already installed on the appliance.
Do not make the connection too tight.
The regulator is die cast. Overtightening
may crack the
regulator resulting in a gas leak and possible fire or
explosion.
The gas supply between the shutoff valve and the
regulator may be connected
by rigid piping or by
9