NOTE: Read the entire instruction manual before starting the
installation. Refer to Split-System Air Conditioner Common
Installation and Start-Up Practices (included in this packet).
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions thor-
oughly and follow all warnings or cautions included in literature
and attached to the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal word DANGER, WARNING, or CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage.
Before installing, modifying, or servicing system, main elec-
trical disconnect switch must be in the OFF position. There
may be more than 1 disconnect switch. Lock out and tag
switch with a suitable warning label. Electrical shock can
cause personal injury or death.
INSTALLATION
Step 1—Mount Unit to Pad
Refer to Fig. 1 for pad dimensions and dimensions needed to
mount unit to pad.
Step 2—Refrigerant Tubing
Refer to Fig. 2 for refrigerant tube dimensions and connections.
Step 3—Mechanical Connection (38CKN Models)
1. Cut tubing to the correct length, deburr, and size as necessary,
making sure tube ends are square. If a large burr is evident, the
ID and OD must be deburred to allow tube to bottom in valve.
2. Remove lock nuts and ferrules from plastic bags taped to
service panel. (See Fig. 3.)
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
PC 101
Catalog No. 533-837
Tab 3a 2a
Model Specific Instructions
.
Printed in U.S.A.
38CKB(N), 38CMB, 38BRB
Split-System Air Conditioner
A
UNIT SIZE
38CKB(N)018, 024
38CKB(N)030-042
38CMB018-030
38BRB024-060
38CKB(N)048, 060
38CMB036-060
Fig. 1—Mount Unit to Pad
If undersized, damaged, or elliptically shaped tubing is used
when making connection, leaks could result.
3. Slide the lock nut and ferrule onto each tube. (See Fig. 4.)
4. Apply a few drops of refrigerant oil to the ferrule and valve
threads to reduce assembly torque and assist sealing.
5. Insert tube end into service valve until it bottoms.
6. Push the ferrule into place and hand tighten the nut until an
increase in torque is felt.
7. Mark the nut and tube and tighten 1-1/2 turns from the mark.
(See Fig. 5.) Keep the tube bottomed in the valve while
tightening nut.
NOTE: A backup wrench on the hex part of the suction valve is
required while tightening.
Form 38CKB-1SI
"D. (9.53) TIEDOWN
3
8
KNOCKOUTS (2) PLACES
B
TIEDOWN KNOCKOUT
LOCATIONS
MIN. PAD
DIM. (IN.)
A
B
(In.)
(In.)
18 X 18
3
15
22-1/2 X 22-1/2 3-11/16 18-1/8
30 X 30
6-1/2
23-1/2
Pg 1
2-95
Replaces: New
C
A94199
C
(In.)
10-3/16
14-3/8
20

Advertisement

loading

Summary of Contents for Carrier 38CKN

  • Page 1 Refer to Fig. 2 for refrigerant tube dimensions and connections. tightening nut. NOTE: A backup wrench on the hex part of the suction valve is Step 3—Mechanical Connection (38CKN Models) required while tightening. 1. Cut tubing to the correct length, deburr, and size as necessary, making sure tube ends are square.
  • Page 2 VALVE FITTING FERRULE TUBING MARK ON LOCK NUT AND TUBE A92122 Fig. 5—Proper Marking of Valve Assembly (38CKN) Step 4—Install Solenoid Valve In Liquid Tube (If Re- quired) LOCK NUT A92120 Fig. 3—Mechanical Fitting Assembly (38CKN) Not all applications require use of a liquid tube solenoid valve.
  • Page 3 6.) The solenoid valve is to be installed a maximum of 2 ft ELECTRICAL JUNCTION from indoor coil. ELECTRICAL COIL Avoid valve damage while brazing by wrapping valve with a heat-sinking material such as a wet cloth. 3. Braze valve onto end of liquid tube using silver bearing or non-silver bearing brazing material.
  • Page 4 [ ] Classroom Service Training A94328 Copyright 1995 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 38ckb1si Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

This manual is also suitable for:

38ckb38cmb38brb