Mitsubishi Electric PEAD-RP35EA Service Manual page 30

Hide thumbs Also See for PEAD-RP35EA:
Table of Contents

Advertisement

10-5. HOW TO CHECK THE PARTS
Parts name
Room temperature
Disconnect the connector then measure the resistance using a tester.
thermistor
(TH1)
(Surrounding temperature 10:~30:)
Pipe temperature
thermistor
(TH2)
Condenser/Evaporator
temperature thermistor
(TH5)
<Thermistor Characteristic graph>
Thermistor for
lower temperature
Thermistor R
=15k" ± 3%
0
Fixed number of B=3480k" ± 2%
Rt=15exp { 3480(
273+t
0:
15k"
10:
9.6k"
20:
6.3k"
25:
5.2k"
30:
4.3k"
40:
3.0k"
30
Normal
4.3k"~9.6k"
Open or short
Room temperature thermistor(TH1)
Pipe temperature thermistor(TH2)
Condenser/evaporator temperature
thermistor(TH5)
1
1
) }
273
Check points
Abnormal
(Refer to the thermistor)
< Thermistor for lower temperature >
50
40
30
20
10
0
-20 -10 0
10 20 30 40 50
Temperature (:)